The Daikin Indoor Cooling/Heating Unit FXMQ24PBVJU is a versatile HVAC solution designed for efficient climate control in residential and commercial spaces. This model offers reliable heating and cooling performance, ensuring optimal comfort throughout the year. Regular maintenance is essential for longevity and efficiency.
Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more
Daikin Indoor Cooling/Heating Unit FXMQ24PBVJU
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Electronic Expansion Valve Coil Check
Warning: This procedure requires trained personnel with PPE!
Electronic Expansion Valve Coil checked
Remove the connector for electronic expansion valve (X7A) from PCB
Measure the resistance value between pins
No continuity between White and Yellow
Resistance value between White and Orange
Resistance value between White and Orange is approx. 300 Ω
Resistance value between White and Red
Resistance value between White and Red is approx. 150 Ω
Heat Recovery System Maintenance
Check for High Pressure in cooling
Check for High Pressure in heating
Check Thermistor
Check Pressure Sensor
Check for broken wire of the relay wire
Procedure for checking outdoor-outdoor unit transmission wiring for broken wires
Turn OFF the power supply to all equipment
Short circuit between the outdoor-outdoor unit terminal F1 and F2 in the 'Outdoor Unit A'
Conduct continuity checks between the transmission wiring terminal blocks F1 and F2 of the central remote controller using a multimeter
Heat Recovery System Vacuuming/Dehydration Maintenance
Normal vacuuming and dehydration
Vacuum pump connected to service ports of liquid pipe and gas pipe
Enter the vacuum level after 2 hours of vacuuming
Did the vacuum level reach –100.7 kPa (–14.6 psi) or less?
Enter the vacuum level after additional 1 hour of vacuuming if needed
Did the vacuum level reach –100.7 kPa (–14.6 psi) or less after additional vacuuming?
Leak tests conducted if vacuum level did not reach the required level
Compressor left at the degree of vacuum of –100.7 kPa (–14.6 psi) or less for a period of 1 hour or more
Enter the vacuum gauge reading after 1 hour
Power Transistor Check
Power OFF
All wiring removed from the PCB where power transistors are mounted on
Type of multimeter prepared
Power supply turned OFF
Measurement of resistance made after a lapse of 10 minutes or more
Measurement made in resistance measurement mode in the x1 kΩ range when using the analog type of multimeter
Measurement made in diode check mode when using the digital type of multimeter
Sign off on the power transistor check
Pressure Check
Warning: This procedure requires trained personnel with PPE!
Compressor PI control in cooling
Low pressure protection control
Hot gas bypass control
Superheated degree control by indoor unit electronic expansion valve in cooling
Superheated degree control by outdoor unit electronic expansion valve in heating
Enter the low pressure reading
Enter the high pressure reading
Sign off on the pressure check
Access the parts list for your equipment in MaintainX.
Junction Pipe Kit
KHRP26A250T
Junction Pipe Kit
KHRP26A250T
Junction Pipe Kit
KHRP26A250T
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX