Turn manuals into instant answers
with your AI-powered assistantTurn manuals into instant answers
with your AI-powered assistant
Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.
Find all the essential guides in one place.
Tensioning Guide
Belt-diagram
C-120 pulleys
+ 13 more
Pre-built workflows to keep your asset running smoothly.
Daily Electrical System Inspection
Replace Roller and Pulley
Install Engine B-120
+ 29 more
Integrate maintenance plans directly into your work orders.
Motion Industries
Applied Industrial Technologies
Electrical Brothers
+ 5 more
Access the parts list for your equipment in MaintainX.
Drive Motor
B2 Rollers
Tensioning System
+ 40 more

Daikin Cooling-Only Outdoor Unit RKS36HVJU
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Capacitor Voltage Check
Warning: Check the main circuit for short circuit before proceeding
Main circuit checked for short circuit?
Warning: Be careful never to touch any live parts.
Voltage reading of the capacitor
Sign off on the voltage check
Electronic Expansion Valve Check
Warning: This check requires trained personnel with PPE!
EV connector correctly connected to the PCB
Did the EV generate latching sound after power cycle?
Continuity confirmed when connector disconnected and tested with a tester
Check the continuity between the pins
EV coil faulty if no continuity between the pins
Outdoor unit PCB faulty if continuity confirmed
Note: The latching sound varies depending on the valve type.
Sign off on the electronic expansion valve check
Fan Motor Connector Output Check
Check the connection of connector
Check the motor power supply voltage output (pins 4 - 7)
Check the motor control voltage (pins 4 - 3)
Check the rotation command voltage (pins 4 - 2)
Check the rotation pulse (pins 4 - 1)
Sign off on the fan motor connector output check
Inverter Checker Check
Warning: This procedure involves high voltage. Only trained personnel should perform it.
Power turned off
Install the inverter checker instead of a compressor
Voltage of the built-in smoothing electrolytic capacitor dropped to 10 VDC or below
Terminals removed from the compressor
Terminals connected to the terminals of the inverter checker
Warning: Do not touch the terminals (U,V,W) each other. High voltage is applied.
Power transistor test operation activated from the outdoor unit
Diagnose according to 6 LEDs lighting status
Power Module Check
Check No.22
Note: Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is approx. 0 V before checking.
Voltage between (+) and (–) of the diode bridge (DB1) is approx. 0 V
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the connector, press the protrusion on the connector.
Compressor harness connector disconnected from the outdoor unit PCB
Follow the procedure below to measure resistance between the terminals of the DB1 and the terminals of the compressor with a multi-tester. Evaluate the measurement results for a judgment.
Enter the resistance between the terminals of the DB1 and the terminals of the compressor
Resistance measurement within acceptable range
Sign off on the power module check
Access the parts list for your equipment in MaintainX.
Inverter Checker
1225477
Silicon Grease
1172698
Inverter Checker
1225477
Silicon Grease
1172698
Inverter Checker
1225477
Silicon Grease
1172698
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX