Bell & Gossett Pump 80-SC 5 × 5 × 9½
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Pump Startup Check
Preparation for startup
Verify driver settings before starting the pump
Ensure warm-up rate does not exceed 2.5°F (1.4°C) per minute
Flush and clear the system to remove dirt or debris
Bring variable-speed drivers to rated speed quickly
Run new or rebuilt pump at speed for flushing and cooling
Is the pump temperature within 100°F (38°C) of the fluid temperature?
Circulate fluid through the pump for warming up
Uncouple unit if settings are not verified
Piping Check
Piping checklist
Ensure all piping components are correctly installed and supported
Mechanical Seal Maintenance
Replace the seal
Remove the coupling guard
Remove the flush line from the seal cap
Is it an outside seal?
Remove the coupler halves
Tape the collar rings together in pairs as assembled previously
Remove the seal cap or seal gland through the space between shafts
Remove the seal seat from the seal cap or gland
Is it an inside seal?
3 Monthly Shaft Storage Maintenance
Long-term storage
Store in a covered and dry location
Store the unit free from heat, dirt, and vibrations
Rotate the shaft by hand several times at least every three months
Treat bearing and machined surfaces so that they are well preserved
Refer to the drive unit and coupling manufacturers for their long-term storage procedures
Contact your local sales and service representative for questions about possible long-term storage treatment services
Pump Maintenance
Disassembly precautions
Ensure the pump is isolated from the system and pressure is relieved before disassembly.
Disconnect and lock out power to the driver before performing any installation or maintenance tasks.
Use proper lifting methods and wear steel-toed shoes at all times.
Ensure all replacement parts are available before disassembling the pump for overhaul.
Drain the pump
Allow all system and pump components to cool before handling.
Close the isolation valves on the suction and discharge sides of the pump.
Open the drain valve and ensure liquid stops coming out before proceeding.
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.