AERCO International Boiler Benchmark 2000
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
12 Monthly Air Filter Maintenance
Warning: This maintenance check requires trained personnel with PPE!
Is the boiler operational?
If boiler is not operational, report the issues to the maintenance team and stop the procedure
Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit.
Remove the top shroud from the unit by grasping the top handle and lifting straight up. This will disengage the shroud from the four (4) pins in the side panels.
Refer to Figure 7-7 and locate the air filter attached to the air/fuel valve inlet.
Using a flat-tip screwdriver or 5/16” nut driver, loosen the clamp securing the filter to the inlet flange of the air/fuel valve. Remove the filter and clamp.
The filter may be cleaned in hot soapy water to remove oil and dirt. The filter should be thoroughly dried and then sprayed with a light coating of oil, such as WD-40, prior to reinstallation.
Each replacement air filter is equipped with its own clamp. Therefore, simply install the replacement air filter on inlet flange of the air fuel valve and tighten the clamp with a flattip screwdriver or 5/16” nut driver.
12 Monthly Condensate Drain Trap Maintenance
Warning: To avoid personal injury, ensure that the following guidelines are strictly observed before servicing:
Disconnect the AC supply by turning off the service switch and AC supply circuit breaker.
Shut off the gas supply at the manual shut-off valve provided with the unit.
Allow the unit to cool to a safe water temperature to prevent burning or scalding.
Did you disconnect the external condensate trap by loosening the union pipe connection between the trap and the exhaust manifold drain pipe?
Did you remove the connections on the inlet and outlet sides of the condensate trap?
Did you loosen the four thumbscrews securing the cover on the condensate trap and remove the cover?
Did you remove the float from the condensate trap?
Did you remove the O-ring and orifice gaskets from the trap?
1 Daily Boiler Test
WARNING: Periodic testing of all boiler controls and safety devices is required to determine that they are operating as designed. Precautions shall be taken while tests are being performed to protect against bodily injury and property damage. The owner or user of an automatic boiler system should set up a formal system of periodic preventive maintenance and testing. Tests should be conducted on a regular basis and the results recorded in a log-book.
Gauges, monitors and indicators: Visual inspection and record readings in operator log
Instrument and equipment settings: Visual check against factory recommended specifications
Sign off on the daily boiler test
1 Monthly Boiler Test
WARNING: Periodic testing of all boiler controls and safety devices is required to determine that they are operating as designed. Precautions shall be taken while tests are being performed to protect against bodily injury and property damage. The owner or user of an automatic boiler system should set up a formal system of periodic preventive maintenance and testing. Tests should be conducted on a regular basis and the results recorded in a log-book.
Flue, vent, stack or intake air duct: Visually inspection condition and check for obstructions
Low air flow: See section 6.8
1. Disable the blower output drive voltage as follows:
(a) Press the MENU key until CONFIGURATION MENU is displayed.
(b) Press the ▲ arrow key until the ANALOG OUTPUT function is displayed, then press the CHANGE key.
(c) Press the ▼ arrow key until OFF is displayed, then press the ENTER key.
2. Start the unit in the Manual Mode at a valve position between 25% and 30%.
3. The unit should shut down and lockout, showing AIRFLOW FAULT DURING PURGE in the display.
1 Weekly Boiler Test
WARNING: Periodic testing of all boiler controls and safety devices is required to determine that they are operating as designed. Precautions shall be taken while tests are being performed to protect against bodily injury and property damage. The owner or user of an automatic boiler system should set up a formal system of periodic preventive maintenance and testing. Tests should be conducted on a regular basis and the results recorded in a log-book.
Instrument and equipment settings: Verify factory settings
Spark Igniter-Injector:
1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from the unit
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up. This will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the cable from the igniter-injector (Figure 7-1).
4. Refer to the partial exploded view in Figure 7-2. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector tube of the igniter-injector to the elbow of the staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector.
5. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end wrench.
6. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence of substantial erosion or carbon build-up, the igniter-injector should be replaced. If carbon build-up is present, clean the component using fine emery cloth. Repeated carbon buildup is an indication that the combustion settings of the unit should be checked. Refer to Chapter 4 for combustion calibration procedures.
Access the parts list for your equipment in MaintainX.
100 Ps
58087-4
125 Psi
58087-7
12V Power Suply
65109
1/4" Bolt Size Flat Washer
123626
1/4" Npt Mxf Brass Ball Valve
92077
100 Ps
58087-4
125 Psi
58087-7
12V Power Suply
65109
1/4" Bolt Size Flat Washer
123626
1/4" Npt Mxf Brass Ball Valve
92077
100 Ps
58087-4
125 Psi
58087-7
12V Power Suply
65109
1/4" Bolt Size Flat Washer
123626
1/4" Npt Mxf Brass Ball Valve
92077
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX