Trane CenTraVac™ Water-Cooled Chiller CVHF - 1070-1300 - 1062 - 210L / 210L
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
1 Yearly Control Circuits Inspection
- Shut down the chiller once each year to check the items of Control Circuits
1. Verify control parameters
2. Test appropriate sensors for accuracy
3. Ensure sensors are properly seated in wells with thermopaste installed
4. Check evaporator leaving water temperature low temperature cutout setpoint
5. Condenser high pressure switch check-out
6. Check adjustment and operation of the inlet guide vane actuator;
1 Yearly Exterior Parts Maintenance
- Shut down the chiller once each year to check the items of Exterior
1. Inlet guide vane linkage
2. Clean and touch-up painted surfaces as needed
3. Repair deteriorated, torn, or missing insulation;
1 Yearly Chiller Maintenance
- For R-123 chillers, perform the annual maintenance procedures referred to in Operation and Maintenance Guide: EarthWise Purge System with Tracer AdaptiView Control for Water-Cooled CenTraVac Chillers with R-123 Refrigerant (PRGF- SVX01*-EN). For R-514A chillers, perform the annual maintenance procedures referred to in Operation and Maintenance Guide: Purge System with Tracer AdaptiView Control for Water-Cooled CenTraVac Chillers with R-514A Refrigerant (PRGG-SVX001*-EN)
- Use an ice water bath to verify the accuracy of the evaporator refrigerant temperature sensor (4R10). If the sensor is exposed to temperature extremes outside its normal operating range (0°F to 90°F [-17.8°C to 32.2°C]), check its accuracy at six-month intervals
- Inspect the condenser tubes for fouling; clean if necessary
- Inspect and clean the ifm efector® flow detection sensors. Use Scotch-Brite® or other non-abrasive material to clean scale; do NOT use steel wool, which could cause the probe to rust
- Submit a sample of the compressor oil to a Trane- qualified laboratory for comprehensive analysis
- Measure the compressor motor winding resistance to ground; a qualified service technician should conduct this check to ensure that the findings are properly interpreted. Contact a qualified service organization to leak-test the chiller; this procedure is especially important if the system requires frequent purging;
1 Yearly Starter/Adaptive Frequency Drive Inspection
- Shut down the chiller once each year to check the items of Starter or Adaptive FrequencyTM Drive
1. Inspect starter contacts
2. Check all connections per manufacturer specifications
3. Follow all manufacturer recommendations for starter or Adaptive FrequencyTM Drive (AFD) maintenance
4. Inspect/clean/service the AFD cooling system (water- or air-cooled AFD)
5. Record all applicable starter or starter component settings;
1 Daily Chiller Maintenance
- Check the chiller’s evaporator and condenser pressures, oil tank pressure, differential oil pressure, and discharge oil pressure
- Compare the readings with the values provided in the general maintenance
- Check the oil level in the chiller oil sump using the two sight glasses provided in the oil sump head. When the unit is operating, the oil level should be visible in the lower sight glass
- Complete logs on a daily basis.
Access the parts list for your equipment in MaintainX.
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
Safety Hoist Ring 3/4-10, CTV Unit
RNG01884
Safety Hoist Ring 1/2-13, CTV Unit
RNG01885
Evap Lifting Fixture, CTV Unit
BAR00400
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX