MAMAC Systems Low Pressure Sensor PR-275-R3-MA
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Low Pressure Sensor Checkout
Verify that the unit is mounted in the correct position
Verify appropriate input signal and supply voltage
Verify appropriate configuration range
Transducer Operation Check
Adjust the pressure to obtain maximum output signal for appropriate range
Enter the maximum output signal
Is the maximum output signal within the expected range (20 mA or 5 or 10 VDC)?
Adjust the pressure to obtain minimum output signal
Enter the minimum output signal
Unit Wiring
Caution
Ensure hot wire is on the [+] terminal if using grounded AC
Use an isolation transformer if controller lacks built-in isolation
Avoid powering from transformers used for non-isolated full-wave rectifier power supplies
Connect all 24G power leads to the same power lead on all devices when using multiple units
Maintain correct phasing when powering more than one device from a single transducer
Wiring PR-274/275 Units with mA Output
Remove the terminal block from the circuit board
Locate the [+] and [-] terminal markings on the board
Unit Calibration
Calibration of PR-274/275 mA Units
Connect terminals to power source and DVM
Apply low pressure to the unit and adjust trimmer for low output
Apply high pressure to the unit and adjust span trimmer for high output
Repeat low and high pressure adjustments until desired calibration is achieved
Low Pressure Sensor Installation
Safety Precautions
Disconnect power supply before installation to prevent electrical shock and equipment damage.
Make all connections in accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive moisture or corrosive fumes are present.
Ensure NEMA Type 4 housings are used for outdoor installations to provide protection against wind-blown dust, rain, and hose-directed water.
Do not exceed ratings of the device.
Ensure condensate or moisture does not enter pressure sensor ports.
Mounting the Transducer
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX