Daikin Indoor Unit Wall Mounted Type Air Conditioner FTX35K2V1B
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Electronic Expansion Valve Check
EV connector correctly connected to the PCB
EV generates a latching sound when power is turned off and on again
Continuity confirmed when connector is disconnected and checked with a multimeter
Check the continuity between the pins
EV coil is not faulty if there is continuity between the pins
Outdoor unit PCB (main PCB) is not faulty if continuity is confirmed
Sign off on the electronic expansion valve check
Indoor Fan Motor Connector Output Check
Fan motor wire breakdown / short circuit check
1. Check the connector for connection.
2. Turn the power off.
3. Check if each resistance at the phases U - V and V - W is 90 Ω ~ 100 Ω (between the pins; 12 - 9, and between 9 - 6).
Motor control voltage check
1. Check the connector for connection.
2. Check the motor control voltage is generated (between the pins 2 - 3).
Rotation pulse check
1. Check the connector for connection.
Inverter Analyzer Check
Warning: This procedure requires trained personnel with PPE!
Power turned off?
Install an inverter analyzer instead of a compressor
Charged voltage of the built-in smoothing electrolytic capacitor dropped to 10 VDC or below?
Terminals removed from the compressor?
Terminals connected to the terminals of the inverter analyzer without touching each other?
Activate power transistor test operation from the indoor unit
Power turned on?
Pressed the center of the TEMP button and the OFF button on the remote controller at the same time?
Main Circuit Short Check
Warning: Ensure the voltage between (+) and (–) of the diode bridge (DB1) is about 0 V before proceeding
Enter the voltage between (+) and (–) of the diode bridge (DB1)
If the voltage is not about 0 V, stop the procedure and report the issue
Enter the resistance between the pins of the DB1
Is the resistance ∞ or less than 1 kΩ?
If the resistance is ∞ or less than 1 kΩ, a short circuit occurs on the main circuit
Sign off on the main circuit short check
Power Module Check
Warning: Ensure the voltage between (+) and (–) of the power module is about 0 V before proceeding
Compressor harness connector disconnected from the outdoor unit PCB
Procedure to measure resistance between the terminals of the power module and the terminals of the compressor
Enter the resistance measurement
Evaluate the measurement results
Sign off on the power module check
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX