MaintainX Asset Hub logo
EnterprisePricing
Daikin

Daikin Screw Chiller AWV026

Need answers fast?
Explore the manual using AI.

Daikin Screw Chiller AWV026
Daikin Screw Chiller AWV026

Turn manuals into instant answers
with your AI-powered assistant
Turn manuals into instant answers
with your AI-powered assistant

PDF MANUAL

Manual for Daikin Screw Chiller AWV026

MAINTENANCE RESOURCES

Complete asset maintenance, one click away

Get instant access to all the maintenance information you need. Empower technicians to perform preventive maintenance with asset packages, ready to use right out of the box.

Documents

Documents & Manuals

Find all the essential guides in one place.

  • CheckTensioning Guide

  • CheckBelt-diagram

  • CheckC-120 pulleys

  • + 13 more

Work Orders

Work Order Templates

Pre-built workflows to keep your asset running smoothly.

  • CheckDaily Electrical System Inspection

  • CheckReplace Roller and Pulley

  • CheckInstall Engine B-120

  • + 29 more

Procedures

Procedures

Integrate maintenance plans directly into your work orders.

  • CheckMotion Industries

  • CheckApplied Industrial Technologies

  • CheckElectrical Brothers

  • + 5 more

Parts

Parts

Access the parts list for your equipment in MaintainX.

  • CheckDrive Motor

  • CheckB2 Rollers

  • CheckTensioning System

  • + 40 more

Daikin Screw Chiller AWV026

Daikin Screw Chiller AWV026

Create an account to install this asset package.

Maintenance Plans for Daikin Screw Chiller Model AWV026

Integrate maintenance plans directly into your work orders in MaintainX.

3 Monthly Epoxy Coated Coils Cleaning

Check mark

Warning: This cleaning procedure requires trained personnel with PPE!

Check mark

Is the coil free of surface debris?

Check mark

Select the cleaning agent used

Check mark

If grease or oil film is present, it should be removed with the approved cleaning agent before applying CHLOR*RID DTS.

Check mark

Was the entire coil surface thoroughly wetted with the cleaning agent?

Check mark

After the substrate has been thoroughly wetted, the salts will be soluble and it is now only necessary to rinse them off.

Check mark

Was the coil rinsed with a hose?

Check mark

Warning: A pressure washer will damage the fins. The water used for the rinse is recommended to be of potable quality.

Check mark

Was all cleaner residue thoroughly rinsed off?

Run this procedureArrow right

Oil Sump Check

Check mark

Enter the Discharge Temperature

Check mark

Enter the Saturated Oil Temperature

Check mark

Is Discharge Temperature > Saturated Oil Temperature + 5°C?

Check mark

Is Discharge Temperature < Saturated Oil Temperature + 4.5°C?

Check mark

Sign off on the oil sump check

Run this procedureArrow right

Electrical Terminals Check

Check mark

DANGER: Electric equipment can cause electric shock which will cause severe personal injury or death. Turn off, lock out and tag all power before continuing with following service. Panels can have more than one power source.

Check mark

CAUTION: Periodically check electrical terminals for tightness and tighten as required. Always use a backup wrench when tightening electrical terminals.

Check mark

Power turned off, locked out and tagged?

Check mark

Electrical terminals checked for tightness

Check mark

Backup wrench used when tightening electrical terminals

Check mark

Sign off on the electrical terminals check

Run this procedureArrow right

Screw Chiller Pre-Startup Inspection

Check mark

NOTICE: Daikin Applied service personnel or factory authorized service agency must perform initial startup in order to activate warranty. Return the “Screw Compressor Equipment Warranty Form” within 10 working days to Daikin Applied as instructed on the form to obtain full warranty benefits.

Check mark

CAUTION: Most relays and terminals in the unit control center are powered when S1 is closed and the control circuit disconnect is on. Therefore, do not close S1 until ready for startup or the unit may start unintentionally and possibly cause equipment damage.

Check mark

Double check that the discharge shutoff valve and the optional compressor suction butterfly valves are open.

Check mark

Check that the manual liquid line shutoff valves at the outlet of the subcooler coils are open.

Check mark

Check the leaving chilled water temperature set point on the MicroTech® III controller to be sure it is set at the desired chilled water temperature.

Check mark

Start the auxiliary equipment for the installation by turning on the time clock, and/or remote on/off switch, and chilled water pump.

Check mark

Check to see that pumpdown switches Q1 and Q2 are in the “Pumpdown and Stop” (open) position. Throw the S1 switch to the “Auto” position.

Check mark

Under the “Control Mode” menu of the keypad, place the unit into the automatic Cool Mode.

Check mark

Start the system by moving pumpdown switch Q1 to the “Auto” position.

Run this procedureArrow right

Screw Chiller Pre-Start Check

Check mark

Chilled Water:

Check mark

- Piping Complete

Check mark

- Water strainer installed on evaporator, 0.125” (3.2mm) or smaller perforations

Check mark

- Water System filled, flushed and vented

Check mark

- Pumps installed and operational (rotation checked, strainers cleaned)

Check mark

- Controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)

Check mark

- Water system operated and tested; flow meets unit design requirements

Check mark

- Flow switch installed and wired

Check mark

- Vent installed on evaporator

Run this procedureArrow right

Parts for Daikin Screw Chiller AWV026

Access the parts list for your equipment in MaintainX.

Part Name
Part Number

AWG Wire Gauge

83754

AWG Wire

83804

Enviro-Coil Concentrate, Hydro-Balance Corp P.O. Box 730 Prosper, TX 75078 800-527-5166

H-EC01

Chloride Remover, Chlor*Rid Int’l, Inc. P.O. Box 908 Chandler, AZ 85244 800-422-3217

Chlor*Rid DTS

AWG Wire Gauge

83754

AWG Wire

83804

Enviro-Coil Concentrate, Hydro-Balance Corp P.O. Box 730 Prosper, TX 75078 800-527-5166

H-EC01

Chloride Remover, Chlor*Rid Int’l, Inc. P.O. Box 908 Chandler, AZ 85244 800-422-3217

Chlor*Rid DTS

AWG Wire Gauge

83754

AWG Wire

83804

Enviro-Coil Concentrate, Hydro-Balance Corp P.O. Box 730 Prosper, TX 75078 800-527-5166

H-EC01

Chloride Remover, Chlor*Rid Int’l, Inc. P.O. Box 908 Chandler, AZ 85244 800-422-3217

Chlor*Rid DTS

Unlock efficiency
with MaintainX CoPilot

MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.

Time Lapse Icon

Reduce Unplanned Downtime

Ensure your team follows consistent procedures to minimize equipment failures and costly delays.

Wrench Clock Icon

Maximize Asset Availability

Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.

Dollar Coin Icon

Lower Maintenance Costs

Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.

Thousands of companies manage their assets with MaintainX

DuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterrollDuracellAB InBevErgonTitan AmericaMeritUnivar SolutionsRivianCadrexMagnaMaasPresriteSoutheast PowerInterroll

More from Daikin

Explore Other Assets