Daikin VRV X Series High-COP Type Air Conditioner RXQ38AHR
Create an account to install this asset package.
Integrate maintenance plans directly into your work orders in MaintainX.
Air Conditioner Test
Warning: This test operation requires trained personnel with PPE!
INFORMATION: It may take 10 minutes to achieve a uniform refrigerant state before the compressor starts.
During the test operation, the refrigerant running sound or the magnetic sound of a solenoid valve may become loud and the display indication may change. These are not malfunctions.
All front panels are closed
All field settings are set
Power to the outdoor unit and the connected indoor units is ON
NOTICE: Be sure to turn on the power 6 hours before operation in order to protect the compressor
Default (idle) situation is existing
Push BS2 for 5 seconds or more. The unit will start test operation.
Air Conditioner Test Operation Check
Test Operation
Is the temperature setting of the remote controller at the lowest level in cooling mode or in test mode?
Checklist
Is the operation lamp lit?
Is the timer lamp off?
Is the fan operating?
Is the air from indoor unit cool?
Is the air from outdoor unit warm?
Is the air flow from the indoor unit stopped occasionally during operation?
Fan Motor Connector Check
Outdoor unit
Power supply turned OFF
Resistance between phases of U, V, W at the motor side connectors
Values are balanced and there is no short circuiting
Indoor unit: FXMQ50-140PB
X1A connector removed from the fan PCB (A2P)
Resistance between the U and V, V and W, and W and U phases of the motor connector
Each phase are balanced (within a permissible dispersion range of ±20%)
Fan Motor Connector Check (Signal Cable): CHECK 17 Resistance measuring points and judgment criteria.
Power Transistor Check
CHECK 4: Perform the following procedures prior to check.
Power OFF
All wiring removed from the PCB where power transistors are mounted on
Preparation Multimeter
Type of multimeter prepared
Point of Measurement and Judgment Criteria
Power supply turned OFF
10 minutes or more passed since power supply turned OFF
Measurement mode for analog multimeter
Refrigerant Overcharge Check
Warning: This check requires trained personnel with PPE!
Enter the high pressure reading
Is overload control conducted causing insufficient cooling capacity?
Enter the superheating degree of suction gas
Is the compressor lower in discharge pipe temperature despite of pressure loads?
Enter the subcooling degree of condensate
Is the subcooling degree of condensate high?
Sign off on the refrigerant overcharge check
MaintainX CoPilot is your expert colleague, on call 24/7, helping your team find the answers they need to keep equipment running.
Reduce Unplanned Downtime
Ensure your team follows consistent procedures to minimize equipment failures and costly delays.
Maximize Asset Availability
Keep your assets running longer and more reliably, with standardized maintenance workflows from OEM manuals.
Lower Maintenance Costs
Turn any technician into an expert to streamline operations, maintain more assets, and reduce overall costs.
Thousands of companies manage their assets with MaintainX