DEHY 1 DAILY CHECK LIST DOUBLE DUTCH

This daily checklist verifies safe, efficient operation of the DEHY 1 unit by confirming run status and documenting oil level/temperature/differential pressure, separator DP, leaks/vibration, fan condition, drains, instrument gas pressure (>85 psig), valve alignment, and containment closures, with photo evidence where prompted. Technicians record PASS/FLAG/FAIL results to trigger timely corrective actions and maintain reliable dehydration performance.
TULS Dairy
09/03/2025

DEHY 1 DAILY CHECK LIST DOUBLE DUTCH

This daily checklist verifies safe, efficient operation of the DEHY 1 unit by confirming run status and documenting oil level/temperature/differential pressure, separator DP, leaks/vibration, fan condition, drains, instrument gas pressure (>85 psig), valve alignment, and containment closures, with photo evidence where prompted. Technicians record PASS/FLAG/FAIL results to trigger timely corrective actions and maintain reliable dehydration performance.

    Is Dehy running?

    take picture of oil level and check for leaks and valve alignment

    • Yes
    • No
    • N / A

    Dehy Oil Level

    Add or drag pictures

    Dehy Oil Level

    • Pass
    • Flag
    • Fail

    Check Both Scavenger Site Glass (Only the one from the top of vessel should have oil present)

    • Pass
    • Flag
    • Fail

    Check Oil Differential Pressure

    1-25psi change filters at 20psi

    Check Oil Temperature Delta T

    Entering temperature compared to exit temperature of oil

    Check DP on oil gas separator @ Gauge (if DP >6, replace)

    • Pass
    • Flag
    • Fail

    Check Compressor for Oil Leaks, Vibration and Hub Damage

    • Pass
    • Flag
    • Fail

    Check Water Knockout and Drain if Needed.

    • Pass
    • Flag
    • Fail

    Check Air Cooler Fan for noise, debris and vibration.

    • Pass
    • Flag
    • Fail

    Check DrainAll Pneumatic Pump to ensure it is operating correctly.

    • Pass
    • Flag
    • Fail

    Instrument Gas Pressure (SP >85psig)

    • Pass
    • Flag
    • Fail

    Instrument Gas Pressure (SP >85psig)

    Add or drag pictures

    Are Oil Containment Valve/Plugs closed?

    • Pass
    • Flag
    • Fail

    Check Valving alignment on piping

    • Pass
    • Flag
    • Fail
Source: TULS Dairy (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.