Back

W&H Cast Line 7-9 – Maintenance – 15000 h (20 months)

Inspection and battery replacement of your equipment.
MALPACK
05/17/2023

W&H Cast Line 7-9 – Maintenance – 15000 h (20 months)

Inspection and battery replacement of your equipment.

    Industrial PC Automation PC810: Replacing the battery

    - Replace the battery (1) in the automation PC. Interval: 15,000 hours Use: 3V / 950 mAh battery The instructions in the sub-vendor documentation must be adhered to. - Open the battery compartment and remove the battery by pulling on the extraction strip. (1) Battery Reference: 8.1.2 Eltainer

    • Capture.PNG
    • Pass
    • Flag
    • Fail

    Service PC Automation PC910: Replacing the battery

    - Replace the battery (1) in the automation PC. Interval: 15,000 hours Use: 3V / 950 mAh battery The instructions in the sub-vendor documentation must be adhered to. - Open the battery compartment and remove the battery by pulling on the extraction strip. (1) Battery Reference: 8.1.2 Eltainer

    • Capture.PNG
    • Pass
    • Flag
    • Fail

    8.1.3 X20 Controller: X20 controller

    WARNING: Risk of injury from electrical current. *Only ever carry out maintenance works after the machine has been de-energized. Only skilled electricians are allowed to maintain the controller* KEEP IN MIND: The mounting location of the X20 controllers can be taken from the electrical circuit diagrams. Not all of the X20 controllers have a battery. Which of the X20 controllers have a battery can be taken from the sub-vendor documentation. To prevent data losses the battery should be replaced withou one minute. - Replace the battery (1) in all X20 controllers. Interval: 15,000 hours Use: 3V / 950 mA battery The instructions in the sub-vendor documentation must be adhered to. (1) Battery Reference: 8.1.3 X20 controller

    • Capture.PNG
    • Pass
    • Flag
    • Fail

    X20 control: Replacing the battery

    KEEP IN MIND: Please heed the manufacturer's instructions. The X20 control is integrated in control power box +E2x. - Replace the lithium battery (1). Interval: 15,000 hours Use: 3V / 950 mA lithium battery (1) Lithium battery Reference: 8.3.1 Extruder 70

    • Capture.PNG
    • Pass
    • Flag
    • Fail
Source: MALPACK (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.