Resetting Rinks Compressor SOP

A standard operating procedure for safely resetting the rinks compressor following a fault or shutdown, guiding operators through the correct verification and restart sequence to restore reliable refrigeration performance and return the ice-making system to full operational service.
Chelsea Piers Connecticut
07/29/2026

Resetting Rinks Compressor SOP

This procedure outlines the process for safely restarting rink compressors that have gone into alarm, including verifying that the compressor room is safe to enter, clearing faults, checking VFDs and breakers if needed, and restoring power. It also guides you through resetting the required system controls and equipment to Automatic or Start Online as appropriate to return the refrigeration system to normal operation, while emphasizing that the MOD or ARC 24-hour service hotline (978-474-4000) should be contacted if ammonia is present, assistance is needed, or it is unsafe to proceed.

    Make Sure It is Safe to Enter Compressor Room

    • 20260729_145038.jpg

    If there is ammonia present, immediately call MOD

    Clear Fault

    • 20260729_1354223.jpg
    • 20260729_1354222.jpg

    Check VFDs and Breakers

    • 20260729_1354342.jpg

    If you suspect VFD is faulted or Breaker is Flipped, perform this section. If not, skip to next section.

    If you have any questions or feel unsafe, call ARC 24 hour service hotline at 978-474-4000

    Open Doors 1-2 to access VFDs

    • 20260729_1355062.jpg

    Open Door 4 to access Breakers (You will need a flathead screwdriver to disengage the lock)

    • 20260729_135539.jpg

    Close all doors and turn main power switch back on

    Restarting Compressors

    • 20260729_135610.jpg
    • 20260729_1356512.jpg
    • 20260729_1357282.jpg
    • 20260729_135735.jpg
    • 20260729_1357592.jpg
    • 20260729_135804.jpg
    • 20260729_1358222.jpg
    • 20260729_135833.jpg
    • 20260729_1358512.jpg
    • 20260729_135912.jpg
    • 20260729_1359242.jpg
    • 20260729_135929.jpg
    • 20260729_1359442.jpg
    • 20260729_1359542.jpg
    • 20260729_140000.jpg
    • 20260729_1400092.jpg
    • 20260729_1359542.jpg
    • 20260729_1400122.jpg
    • 20260729_1359542.jpg
Source: Chelsea Piers Connecticut (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.