AT24-05 Monthly Calibration
This procedure verifies that all machine power supplies operate within specified voltage ranges. Using a calibrated meter, readings are taken and documented to ensure equipment accuracy and proper machine performance.
AT24-05 Monthly Calibration
Calibration Procedure
40. Measure the voltage at the 24.00vdc power supply. (23.7vdc - 24.2vdc)
Meter name
Unit
50. Measure the voltage at the 12.00vdc power supply. (11.8vdc - 12.3vdc)
Meter name
Unit
60. Measure the voltage at the 5.00vdc power supply. (4.8vdc - 5.3vdc)
Meter name
Unit
70. Inside station #4 left side enclosure measure the voltage between the GND connection and positive 12vdc power connection. (11.7vdc - 12.2vdc)
Meter name
Unit
80. Measure the voltage between the GND connection and positive +5vdc power connection. (4.8vdc - 5.2vdc)
Meter name
Unit
90. Measure the voltage between the GND connection and positive 6.2vdc power connection. (6.1vdc - 6.5vdc)
Meter name
Unit
100. Inside the station #6 right side enclosure measure the voltage between the GND connection an the positive 12vdc power connection. (11.7vdc - 12.2vdc)
Meter name
Unit
110. Measure the voltage between the GND connection and +5vdc power connection. (4.8vdc - 5.3vdc)
Meter name
Unit
120. measure the voltage between the GND connection and positive 6.2vdc power connection and document it on the spreadsheet. (5.6vdc - 6.8vdc)
Meter name
Unit
170. Enter the ID# of the voltage meter that was used.
180. Sign Off
Click here to sign