Monthly Fire System Preventive Maintenance
This procedure outlines the monthly preventive maintenance tasks for the fire suppression system in the mill. It includes safety checks, cleaning, inspection, testing of system components, and recording of spark counts across different zones.
Monthly Fire System Preventive Maintenance
This procedure outlines the monthly preventive maintenance tasks for the fire suppression system in the mill. It includes safety checks, cleaning, inspection, testing of system components, and recording of spark counts across different zones.
Safety and Preparation
Gather tools and materials
Clean and Inspection
Zone 1 & 2
Clean sensor lens on spark detection system with alcohol and inspect for wear or cracks
Flush out water lines on spark detection system at each 'Y' strainer until water is clean
Test both valves in Card 1
Test Both sensors in Card 1 If failed Note which zone(s)
Inspect valve and heat tape on spark detection system for proper temperature and absence of oil or grease
Exercise solenoid valve on deluge system to ensure proper orientation
Test deluge system functionality from diagnostic screen on main control panel
Test boost pump functionality from diagnostic screen control panel
Clean and Inspection
Zone 3 & 4
Clean sensor lens on spark detection system with alcohol and inspect for wear or cracks
Flush out water lines on spark detection system at each 'Y' strainer until water is clean
Test both valves in Card 2
Test Both sensors in Card 2 If failed Note which zone(s)
Inspect valve and heat tape on spark detection system for proper temperature and absence of oil or grease
Exercise solenoid valve on deluge system to ensure proper orientation
Test deluge system functionality from diagnostic screen on main control panel
Test boost pump functionality from diagnostic screen control panel
Clean and Inspection
Zone 5
Clean sensor lens on spark detection system with alcohol and inspect for wear or cracks
Flush out water lines on spark detection system at each 'Y' strainer until water is clean
Test valves in Card 3
Test Both sensors in Card 3 If failed Note which zone(s)
Inspect valve and heat tape on spark detection system for proper temperature and absence of oil or grease
Exercise solenoid valve on deluge system to ensure proper orientation
Test deluge system functionality from diagnostic screen on main control panel
Test boost pump functionality from diagnostic screen control panel
Record Spark Counts for All Zones
Zone 1: Enter spark count
Zone 2: Enter spark count
Zone 3: Enter spark count
Zone 4: Enter spark count
Zone 5: Enter spark count
Completion
Additional notes (if necessary)
Completed by
Click here to sign