Back

Daily Critical Reliability Checklist

Use the guideline and complete checklist below to ensure information is documented and the correct temperature and levels are checked at all times.
24P DC Columbus - Cintas
07/25/2023

Daily Critical Reliability Checklist

Use the guideline and complete checklist below to ensure information is documented and the correct temperature and levels are checked at all times.

    Record boiler pressure: (75 to 100 PSIG)

    Meter name
    Unit

    Check boiler chemical levels

    • Pass
    • Flag
    • Fail

    Test/record boiler water chemistry

    • Pass
    • Flag
    • Fail

    Test low water cut-off alarm. Document on FM Global Red Tag System

    • Pass
    • Flag
    • Fail

    Record stack temperature on boiler. Max: 475 F

    Meter name
    Unit

    Record feed water tank temperature: (180 F-200 F)

    Meter name
    Unit

    Ensure feed water pumps are running and feed water tank level is adequate

    • Pass
    • Flag
    • Fail

    Check boiler flame condition (should be mostly blue)

    • Pass
    • Flag
    • Fail

    Record water hardness after polishing softener. (0 PPM)

    Meter name
    Unit

    Record compressor pressure (100-125 PSIG)

    Meter name
    Unit

    Record air compressor airend temperature

    Meter name
    Unit

    Check compressor cooling air filter present/clean

    • Pass
    • Flag
    • Fail

    Check oil level is normal (range specified by OEM)

    • Pass
    • Flag
    • Fail

    Check air dryer is running

    • Pass
    • Flag
    • Fail

    Check air tank blow-down is operating properly

    • Pass
    • Flag
    • Fail

    Inspect all water pumps for leaks

    • Pass
    • Flag
    • Fail

    Inspect integrity of shaker screen

    • Pass
    • Flag
    • Fail

    Record tempered water temperature (70-100 F)

    Meter name
    Unit

    Record hot water temperature (140-160 F)

    Meter name
    Unit

    Check water levels in hot and tempered storage tanks

    • Pass
    • Flag
    • Fail

    Check that EQ tank blower/mixer is running (if applicable)

    • Pass
    • Flag
    • Fail

    Check that pit mixer/blower is running (if applicable)

    • Pass
    • Flag
    • Fail

    Check that WW chemistry mixer is running (if applicable)

    • Pass
    • Flag
    • Fail

    Ensure wash alley trench screen is cleaned

    • Pass
    • Flag
    • Fail

    Record temperature of city water in / city water out

    Record temperature of WW water in / WW water out

    Calculate and record approach reading (Approach = WW water in - city water out)

    With softener, record softener output water hardness (<3 grains)

    Meter name
    Unit

    Record city water reading (High flow)

    Meter name
    Unit

    Record city water reading (Low flow)

    Meter name
    Unit

    Record electrical reading

    Meter name
    Unit

    Record natural gas reading

    Meter name
    Unit
Source: 24P DC Columbus - Cintas (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.