Back

EMTOS Quarterly Preventative Maintenance Report

This procedure outlines the steps for conducting quarterly preventative maintenance on the EMECS asset, including inspection, cleaning, and finalization actions. This provides enhanced safety, operational reliability, and regulatory compliance by proactively identifying and addressing equipment issues before they cause failures. This reduces downtime, extends asset lifespan, and lowers long-term repair costs.
Envent Corporation
10/22/2025

EMTOS Quarterly Preventative Maintenance Report

This procedure outlines the steps for conducting quarterly preventative maintenance on the EMECS asset, including inspection, cleaning, and finalization actions. This provides enhanced safety, operational reliability, and regulatory compliance by proactively identifying and addressing equipment issues before they cause failures. This reduces downtime, extends asset lifespan, and lowers long-term repair costs.
Procedure Max Score: 140

    EMTOS Quarterly PM

    Date

    Inspectors

    Unit #

    License Plate #

    Unit Hours Start

    Air Compressor Hours Start

    Gas Meter Start

    No Power on Unit

    1. Trailer

    Inspect leg stands and grease all Zerk fittings. Check firebox to trailer bolts and holes for integrity. Ensure BIT inspection (California only), Annual inspection and Registration ate up to date, communicate to the mechanic and shop supervisor if due.

    • Pass
    • Flag
    • Fail

    2. Bonding and Grounding

    Check all bonding and grounding cables for good wire, proper clamps, and connections. Each unit should have at least one ground and two bonding spools. With an Ohms meter, check continuity; the reading should be less than 5

    • Pass
    • Flag
    • Fail

    3. Fire Extinguishers

    Verify that the two fire extinguishers on the unit are ready to use, not damaged, the seal is intact, the UL tag is in place, and they are up to date on their annual inspection. Replace if needed.

    • Pass
    • Flag
    • Fail

    4. Air Compressor

    If equipped, check air compressor oil, change if necessary, drain tank of any condensation, check belt integrity and replace if needed. AT WHAT HOUR INTERVALS

    • Pass
    • Flag
    • Fail

    5. Process Blower

    Open belt cover and shaft cover, check fan bushings or bearings, fan sheave, motor sheave, and belts for proper integrity and alignment - replace or tighten if needed. Grease process blower motor through zerk fittings. (Only use polyrex Em grease)

    • Pass
    • Flag
    • Fail

    6. Process Blower/ Combustion Blower/ Air Compressor

    Remove electrical motor cover, inspect wire terminations. Repair or replace connectors if needed.

    • Pass
    • Flag
    • Fail

    7. Capsuhelics & Magnehelics

    Ensure all Caps & Mags are reading 0. Adjust or replace if needed.

    • Pass
    • Flag
    • Fail

    8. Flow Tubes (DS-300, DS-400)

    Remove all DS-300/400 and blow out with shop air, inspect and reinsert or replace if needed..

    • Pass
    • Flag
    • Fail

    9. KO Pot

    Ensure sight glass valves are open. Drain KO Pot if necessary. Visually inspect gasket and PI, replace if needed.

    • Pass
    • Flag
    • Fail

    10. Ignitor/Ignition Transformer

    Clean igniter, verify no corrosion on the connection point to transformers or to the igniter. Mark igniter position before removing. Replace if necessary.

    • Pass
    • Flag
    • Fail

    11. UV Scanner

    12. Rotary Gas Meter (Totalizer)

    Ensure the numbers on the pressure indicators and gas totalizer are readable.

    • Pass
    • Flag
    • Fail

    13. Burner

    Verify Burner gaskets are intact (Visual).

    • Pass
    • Flag
    • Fail

    Verify that the modulating actuator moves to high during the 90 second high fire purge and moves to low when the BMS says to start. Ensure no rust/corrosion along linkage arm.

    • Pass
    • Flag
    • Fail

    14. Propane Fuel Train Pressure Gauges

    Check 0-30 PSIG Gauge on Main Fuel Line Upstream of Pancake Regulator. Verify When Valve is Closed and Gauges Removed that Pressure Goes to 0. Replace if Bad.

    • Pass
    • Flag
    • Fail

    Check 0-30" WC Guage on Main Fuel Line Downstream of Pancake Regulator. Verify When Valve is Closed and Gauges Removed that Pressure Goes to 0. Replace if Bad.

    • Pass
    • Flag
    • Fail

    Check 0-30" WC Gauge on Pilot Fuel Line. Verify When Valve is closed and Gauge Removed that Pressure Goes to 0. Replace if Bad.

    • Pass
    • Flag
    • Fail

    Check 0-15" WC Gauge on Pilot Fuel Line. Verify When Valve is closed and Gauge removed that Pressure Goes to 0. Replace if Bad.

    • Pass
    • Flag
    • Fail

    15. Firebox

    Verify that the stack and firebox inlet sample ports are functional.

    • Pass
    • Flag
    • Fail

    16. Maxon or Eclipse Valves (SSOV 1&2)

    Inspect all valve covers and gaskets are in place and tight. If gasket integrity is compromised replace gasket.

    • Pass
    • Flag
    • Fail

    Inspect landed wires on the valve terminal block are in good condition.

    • Pass
    • Flag
    • Fail

    Ensure that all connections are tight and wiring is not frayed.

    • Pass
    • Flag
    • Fail

    Open side cover plate and verify that no water, debris, or foreign mater. If there are signs of water intrusion, get with engineering to inspect further and give path forward on repairs.

    • Pass
    • Flag
    • Fail

    17. Vaporizer

    Check all wiring in vaporizer and make sure connections are secure (recrimp connections if necessary). Check Controller and ensure in good operating condition. Check silicone integrity around pilot ignitor transformer.

    • Pass
    • Flag
    • Fail

    Ensure inlet valve installed properly in TOP position (Look for Tack Weld- Should be on Top).

    • Pass
    • Flag
    • Fail

    Inspect and clean fire ring.

    • Pass
    • Flag
    • Fail

    Pressure Relief Valve, Inspect it and Replace if it is damaged or has not been changed out in 5 years or more. (By Manufacturer)

    • Pass
    • Flag
    • Fail

    Remove top cover held by 6 screws to inspect refractory and doughnut gasket. Ensure doughnut gasket is still in its place and not obstructing the space around tank.

    • Pass
    • Flag
    • Fail

    18. Panels

    Open each panel and tighten every wire termination. Remember, there are multiple panels: Main Control Panel, Ignitor Transformer panel, and LEL readout Auxiliary Panel on some units.

    • Pass
    • Flag
    • Fail

    Check for open holes in each panel and plug them. Address any sign of rust or water intrusion. Ensure each panel is dry and water-tight. At the main control panel verify that LEL sensor wires are not jumpered (Bypassed) and there is a dessicant pack, add if missing or replace if saturated.

    • Pass
    • Flag
    • Fail

    Inspect the condition of every wire, ensure no wire is rubbing against sharp edges, if so, ask an engineer for help.

    • Pass
    • Flag
    • Fail

    Ensure Spiral wrap is placed correctly to protect wires. Ensure the wire tie downs are operational, replace if necessary.

    • Pass
    • Flag
    • Fail

    Power on Unit and Connected to Propane

    Process Blower

    Check motor rotation and observe/ listen for abnormal sounds or vibrations.

    • Pass
    • Flag
    • Fail

    Combustion Blower

    Check motor rotation and observe/ listen for abnormal sounds or vibrations.

    • Pass
    • Flag
    • Fail

    Air Compressor

    If equipped, turn on compressor, check rotation and observe/listen for abnormal sounds or vibration, check for leaks, and verify units stops at ~135psi (main tank)

    • Pass
    • Flag
    • Fail

    Chart Recorder

    Verify proper time and date stamp, and legible temperature recordings. Report if abnormal recordings found.

    • Pass
    • Flag
    • Fail

    Panel Light Check

    Check all buttons and switches as they are turned on to insure that the switch or button is lit when turned on.

    • Pass
    • Flag
    • Fail

    Area Lights

    Ensure all area light work, replace lightbulb if needed, look for and address signs of rust or water.

    • Pass
    • Flag
    • Fail

    Vaporizer

    Check burner ring to ensure all burner parts lit

    • Pass
    • Flag
    • Fail

    Ensure burner ring turns off when vaporizer gets to 120 F of temperature.

    • Pass
    • Flag
    • Fail

    Maxon or Eclipse Valves

    Cycle solenoid valve prior to starting burner and verify that they do not open. Verify that the valves open after starting burner

    • Pass
    • Flag
    • Fail

    Flame Arrestor

    While the blower is on, check differential pressure across FA to ensure it is clean (should not be greater than 5" wc). If differential pressure is greater than 5" WC, remove and clean.

    • Pass
    • Flag
    • Fail

    Rotary Gas Meter

    Check Pressure gauges on rotary meter and read out gauges. Check differential pressure between gauge (In./H20) behind of main gas (pancake) regulator and first gauge on gas meter is less than 10" wc. If greater, change gasket screen on Totalizer.

    • Pass
    • Flag
    • Fail

    Detonation Arrestor

    While the unit is at temperature (both manual and actuated valves are open) check the differential pressure across the DA (should not be greater than 15" wc) and test drain for plugging (open valve and verify suction while the blower is on)

    • Pass
    • Flag
    • Fail

    KO Pot

    Check KO Pot demister pad for plugging - Open bottom drain and verify suction to ensure bottom drain is not plugged and KO Pot is empty.

    • Pass
    • Flag
    • Fail

    Flow Gauges

    Test all flow sensors and verify proper readings based on increasing and decreasing process and total flows

    • Pass
    • Flag
    • Fail

    Process Isolation Valve

    Check integrity of automatic process isolation valve by opening the process manual valve and verify no suction while unit is below 1400F

    • Pass
    • Flag
    • Fail

    Drain moisture in airline to actuator and verify actuator opens valve once temperature is above 1400F

    • Pass
    • Flag
    • Fail

    Process Manual Trim Valves

    Check integrity of 4" process bypass valve and 10" process valve by bringing unit above 1400F with both valves closed and verify no suction at inlet

    • Pass
    • Flag
    • Fail

    Propane Fuel Train

    With unit running and at temperature, soap test all vaporizer connections and entire fuel train

    • Pass
    • Flag
    • Fail

    With unit running and at temperature, trip the unit and ensure the SSOVs close and stop the flow of propane

    • Pass
    • Flag
    • Fail

    Verify that the high and low pressure switches are intact and that the wires are not jumped together

    • Pass
    • Flag
    • Fail

    High PS. If equipped, with hand pump testing port, isolate the switch from the fuel train and use the hand pump port to test the switch to ensure it shuts the unit down

    • Pass
    • Flag
    • Fail

    Low PS, Close the main valve to the vaporizer and burn out line. If equipped with hand pump testing port, isolate the switch from the fuel train and release pressure from line or use a hand vacuum pump to ensure switch turn the unit down.

    • Pass
    • Flag
    • Fail

    Interlock Testing

    Check all Interlocks on unit

    High Limit Temperature

    While BMS is going into purge, change the set point below the chart recorder temperature and verify a "stoppage" in BMS activity

    • Pass
    • Flag
    • Fail

    While unit is running, lower high temperature set point below chart recorder temperature and verify burner shut down.

    • Pass
    • Flag
    • Fail

    UV Scanner

    Remove UV Scanner from unit. Do not expose to direct sunlight. Cover optical lens and ensure that the unit shuts down.

    • Pass
    • Flag
    • Fail

    LEL Analyzer

    Calibrate LEL in accordance with the procedures, verify analyzer is not bypassed by valves or by jumped wires behind LEL controller.

    • Pass
    • Flag
    • Fail

    Test high LEL shutdown by lowering the setpoint to 10%, then apply the span gas to the LEL analyzer and verify unit shuts down

    • Pass
    • Flag
    • Fail

    Process Blower Pressure Switch

    Open cover of pressure switch and verify that sensor is not jumped. Remove tubing from sensor and verify that interlock is tripped on BMS. Verify that one wire is on common and one wire is on NO (normally open).

    • Pass
    • Flag
    • Fail

    Combustion Blower Pressure Switch

    Open cover of pressure switch and verify that sensor is not jumped. Remove tubing from sensor and verify that interlock is tripped on BMS. Verify that one wire is on common and one wire is on NO (normally open).

    • Pass
    • Flag
    • Fail

    FA Temperature Switch

    Remove Temperature switch. Wrap heating element around probe, set temp to 410 degree F. Verify contacts open w/ohms meter at 400 degree F (for test fires check by disconnecting the common wire)

    • Pass
    • Flag
    • Fail

    Firebox

    Analyze entire exterior firebox wall with temperature gun and notate any part of the wall that exceeds 200°F

    • Pass
    • Flag
    • Fail

    Burner

    Verify that the modulating actuator moves to high during the 90 second high fire purge and moves to low when the BMS says to start

    • Pass
    • Flag
    • Fail

    Trailer Deck

    Perfomr a 360 walk around the unit and ensure no tools or fittings were left anywhere on the deck. Ensure it is fit for traveling.

    • Pass
    • Flag
    • Fail

    Spare Parts

    Verify Spare Parts are in Job Box

    if the answer is "empty "

    If spare is not stocked due to inventory, let a Maintenance Tech at the Yard know what needs to be ordered and then list below what this unit does not have.

    End Hours

    Unit End Hours

    Meter name
    Unit

    Air Compressor End hours

    Generator Meter End

    Technician Closure Signature

    Technician Sign Off

    Supervisor Closure Approval Signature

    Supervisor Sign Off

    Click here to sign
Source: Envent Corporation (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.