Back

Coating line red dye scale calibration

Use this procedure when you suspect the amount of red dye being pumped to the coating is not correct.
CorrChoice Coatings
01/13/2023

Coating line red dye scale calibration

Use this procedure when you suspect the amount of red dye being pumped to the coating is not correct.

    Procedure

    Use this procedure when you suspect the amount of red dye being pumped to the coating is not correct. Get a 5 gallon bucket and configure pump to pump 3 gallons into the bucket. Run a pump cycle. After pump cycle completes measure the amount of red dye pumped into the bucket. If it is not correct do the following: - Select the “Calibration” screen from the touch screen on the red dye stand - Empty (remove anything on) the red dye scale. - Push the “Zero” button on the screen - Confirm a tare weight of 165 is in the data entry point marked “Tare Weight” if it is not select the yellow data entry and enter 165. This tare weight is based on an empty tote weight. - Add something to the scale that weights greater than 500lbs. and does not exceed 5000 lbs. The closer to 5000 the better. - Observe the weight from the scale display and enter that value in the “Cal Weight” data enter point on the touch screen. - Press the “Span” button. - Calibration complete.

Source: CorrChoice Coatings (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.