Back

Allied K-Series (2-7.5 KCA): Annual Maintenance

The annual maintenance procedure focuses on B-lubrication, filters and condenser oil. The main purpose of regular maintenance is to ensure that all equipment required for production is operating at 100% efficiency at all times.
MaintainX
08/24/2022

Allied K-Series (2-7.5 KCA): Annual Maintenance

The annual maintenance procedure focuses on B-lubrication, filters and condenser oil. The main purpose of regular maintenance is to ensure that all equipment required for production is operating at 100% efficiency at all times.

    VI-MAINTENANCE

    The unit should be inspected once a year by a qualified service technician.

    A-Filters

    Units are equipped with temporary filters which must be replaced prior to building occupation. See table 25 for correct filter size. Refer to local codes or appropriate jurisdiction for approved filters. Approved filters should be checked monthly and replaced when necessary. Take note of air flow direction marking on filter frame when reinstalling filters.

    C-Lubrication

    All motors are lubricated at the factory. No further lubrication is required.

    • Screenshot2021-02-16at12.03.13PM.png
    • Screenshot2021-02-16at12.02.20PM.png

    E-Condenser Coil

    Clean condenser coil annually with water and inspect monthly during the cooling season.

    Clean the all-aluminum coil by spraying the coil steadily and uniformly from top to bottom. Do not exceed 900 psi or a 45 angle; nozzle must be at least 12 inches from the coil face. Take care not to fracture the braze between the fins and refrigerant tubes. Reduce pressure and work cautiously to prevent damage.

    Clean the all-aluminum coil by spraying the coil steadily and uniformly from top to bottom. Do not exceed 900 psi or a 45 angle; nozzle must be at least 12 inches from the coil face. Take care not to fracture the braze between the fins and refrigerant tubes. Reduce pressure and work cautiously to prevent damage.

    • Screenshot2021-02-16at12.05.23PM.png

    B-Supply Blower Wheel

    Annually inspect supply air blower wheel for accumulated dirt or dust. Turn off power before attempting to remove access panel or to clean blower wheel.

    I-Electrical

Source: MaintainX (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.