Omnizone™ Constant Volume Water-Cooled Cooling Unit 50BVZ: Monthly Maintenance
This monthly maintenance procedure focuses on air filters. It gives you instructions on how to inspect the air filters and how to replace them.
Omnizone™ Constant Volume Water-Cooled Cooling Unit 50BVZ: Monthly Maintenance
0 steps
This monthly maintenance procedure focuses on air filters. It gives you instructions on how to inspect the air filters and how to replace them.
Air Filters
The 50BV single-piece units come with 1-in. filters. The standard 1-in. filters provide lower pressure drop and longer filter service intervals. The 50BV modular units come with 4-in. filters.
Inspect air filters every 30 days and replace filters as necessary.
Replacement filters should have a minimum efficiency rating of MERV 6 per ASHRAE rating procedures and be rated for up to 625 fpm velocity. Job requirements or local codes may specify higher minimum ratings.
Source: Carrier (www.shareddocs.com)