Back

Boiler Log Test

Regularly maintaining your boiler can reduce your energy bills, save money on costly repairs and prevents winter breakdowns. You can also avoid faults with your boiler to keep your area safe.
184 N Milwaukee WI ( Meng Thao )
03/05/2024

Boiler Log Test

Regularly maintaining your boiler can reduce your energy bills, save money on costly repairs and prevents winter breakdowns. You can also avoid faults with your boiler to keep your area safe.

    *** LOTO Confirmation Statement - DO NOT EDIT/REMOVE ***

    All hazardous energy has been isolated using LOTO procedures?

    All potential stored or residual energy has been relieved, disconnected, restrained, lowered, and/or otherwise rendered safe?

    Plant Water Softener Hardness

    Feedwater Polishing Hardness

    Fire Tube Boiler Water

    Conductivity ( Neutralized ) Range 2000-3000

    Conductivity ( Unneutralized ) Range 3000-4500

    Auto Blowdown Reading ( 3000-45000 )

    P - Alkalinity ( 400-900 )

    M - Alkalinity ( 900 Max )

    OH-ALK ( 2P-M ) >200

    Sulfite ( 30-60 )

    Internal Treatment ( 300-800 )

    Condensate

    Conductivity ( < 50 )

    PH ( 7.8 - 9.0 )

    Chemical Pump Setting

    RLT - 4100S

    OS - 3000S

    BFW - 8100S

Source: 184 N Milwaukee WI ( Meng Thao ) (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.