Back

EMECS Quarterly Preventative Maintenance Report

This procedure outlines the steps for conducting quarterly preventative maintenance on the EMECS asset, including inspection, cleaning, and finalization actions.
Envent Corporation
11/06/2025

EMECS Quarterly Preventative Maintenance Report

This procedure outlines the steps for conducting quarterly preventative maintenance on the EMECS asset, including inspection, cleaning, and finalization actions.

    EMECS Quarterly PM

    Date

    Inspectors

    Unit #

    License Plate #

    Unit Hours Start

    Air Compressor Hours Start

    Gas Meter Start

    No Power on Unit

    Trailer

    Inspect leg stands and grease all Zerk fittings. Check firebox to trailer bolts and holes for integrity. Ensure BIT inspection (California only), Annual inspection and Registration ate up to date, communicate to the mechanic and shop supervisor if due.

    • Pass
    • Flag
    • Fail

    Bonding and Grounding

    Check all bonding and grounding cables for good wire, proper clamps, and connections. Each unit should have at least one ground and two bonding spools. With an Ohms meter, check continuity; the reading should be less than 5

    • Pass
    • Flag
    • Fail

    Fire Extinguishers

    Verify that the two fire extinguishers on the unit are ready to use, not damaged, the seal is intact, the UL tag is in place, and they are up to date on their annual inspection. Replace if needed.

    • Pass
    • Flag
    • Fail

    Air Compressor (42-5 Only)

    If equipped, check air compressor oil, change if necessary, drain tank of any condensation liquid, check belts and tighten or replace if needed, and set regulator between 80-90 psig.

    • Pass
    • Flag
    • Fail

    Vapor Blower (Process Blower)

    Remove blower belt cover and check the integrity bearings and belt. Ensure belt tension is 75 Hz for RB 4000 & 4002, per manual. Re-tension it or replace if needed. Grease vapor blower motor through zerk fittings.(Only use polyrex Em grease)

    • Pass
    • Flag
    • Fail

    Combustion Blower

    Remove bearings cover, look for worn parts. Grease any zerk fittings in the motor and bearings if applicable. (Use only polyrex Em grease). Ensure wires are well connected on the motor.

    • Pass
    • Flag
    • Fail

    Capsuhelics & Magnehelics

    Zero all Capsuhelics and Magnehelics, replace if necessary

    • Pass
    • Flag
    • Fail

    Flow Tubes (DS-300, DS-400)

    Remove all DS-300/400 pitot tubes and blow out with shop air, inspect and reinsert or replace if needed.

    • Pass
    • Flag
    • Fail

    Vapor Blower (Process Blower) / Combustion Blower

    Remove electrical motor cover, inspect wire terminations. Repair or replace connectors if needed.

    • Pass
    • Flag
    • Fail

    Ignitor/Ignition Transformer

    Pull out and clean the two igniters, verify no corrosion on the on the tip. Replace if necessary.

    • Pass
    • Flag
    • Fail

    UV Scanner

    Rotary Gas Meter

    Check Pressure gauges and read out gauges, verify that numbers are readable. Verify when valve is closed and gauge removed that pressure goes to 0. Replace if bad.

    • Pass
    • Flag
    • Fail

    Fuel Train (Enrichment Line)

    Open "Y" strainer to check for propane butter. Note: Release pressure first.

    • Pass
    • Flag
    • Fail

    Pressure Indicators (Gauges)

    Ensure all PIs work, verify that the numbers are readable. replace if needed.

    • Pass
    • Flag
    • Fail

    Firebox

    Inspect fire box sight glass windows and clean if dirty (separate from nipple not by opening the union/glass nut)

    • Pass
    • Flag
    • Fail

    Verify that all the sample points are functional.

    • Pass
    • Flag
    • Fail

    8" Manual Valve

    Check functionality of the valve by moving it to fully open and then to the close position. Verify that the indicator moves to the right position.

    • Pass
    • Flag
    • Fail

    8" Manual Valve

    Check functionality of the valve by moving it to fully open and then to the close position. Verify that the indicator moves to the right position.

    • Pass
    • Flag
    • Fail

    Expansion Joints

    Inspect all expansion joints for proper alignment and integrity, ensure not dry rotting. Torke fasteners to 40 ft-lb

    • Pass
    • Flag
    • Fail

    Vaporizer

    Check all wiring in vaporizer and make sure connections are secure (recrimp connections if necessary). Check controller.

    • Pass
    • Flag
    • Fail

    Inspect Level indicator integrity, remove wire cover, look for and address signs of rust or water.

    • Pass
    • Flag
    • Fail

    Pressure Relieve Valve, Inspect it and replace if it is damage or has not been change in 5 years or more (by manufacture)

    • Pass
    • Flag
    • Fail

    Open inlet "Y" strainer to check for propane butter. Note: Ensure no pressure present before taking fittings apart.

    • Pass
    • Flag
    • Fail

    Remove top cover hold by 6 screws, to inspect refractory and doughnut gasket. Ensure doughnut gasket is still in its place and not obstructing the space around tank.

    • Pass
    • Flag
    • Fail

    Conduit

    Inspect all conduit and conduit covers for signs of leaks or exposed wires.

    • Pass
    • Flag
    • Fail

    Panels

    Open each panel and tighten every wire termination, remove the BMS and check terminations. Remember, there are multiple panels. Check for open holes in each panel, look for and address signs of rust or water, ensure each panel is dry and water tight. Add Dessicant packs to panel if missing or replace if saturated.

    • Pass
    • Flag
    • Fail

    Inspect the condition of every wire, ensure no wire is rubbing agains sharp edges, if so, ask an engineer for help. Ensure spiral wire wrap is placed correclty to protect wires. Ensure the wire tie downs are operational, replace if necessary.

    • Pass
    • Flag
    • Fail

    Chart Recorder

    Did all Chart Recorder Checks Pass or Fail?

    • Pass
    • Flag
    • Fail
    if the answer is "oneOf [FAIL]"

    Explain the Failure or Issue

    Power on Unit and Connected to Propane

    Process Blower

    Check motor rotation and observe/ listen for abnormal sounds or vibrations.

    • Pass
    • Flag
    • Fail

    Combustion Blower

    Check motor rotation and observe/ listen for abnormal sounds or vibrations.

    • Pass
    • Flag
    • Fail

    Air Compressor (42-5 Only)

    If equipped, turn on compressor, check rotation and observe/listen for abnormal sounds or vibration, check for leaks, and verify units stops at ~135psi (main tank)

    • Pass
    • Flag
    • Fail

    Chart Recorder

    Verify the display powers up with no error codes or flashing.

    • Pass
    • Flag
    • Fail

    Install chart paper and verify proper time and date stamp, and legible temperature recordings.

    • Pass
    • Flag
    • Fail

    Compare temperature reading with UDC controller readout and verify they are within 50F of each other.

    • Pass
    • Flag
    • Fail

    Panel Light Check

    Check all buttons and switches as they are turned on to insure that the switch or button is lit when turned on.

    • Pass
    • Flag
    • Fail

    Area Lights

    Ensure all area light work, replace lightbulb if needed, look for and address signs of rust or water.

    • Pass
    • Flag
    • Fail

    Vaporizer

    Start vaporizer, ensure all burner ring lit

    • Pass
    • Flag
    • Fail

    Ensure burner ring turns off when vaporizer gets to 120 F of temperature.

    • Pass
    • Flag
    • Fail

    When unit running, Soap test all vaporizer and fuel train fittings.

    • Pass
    • Flag
    • Fail

    SURE 25 Valve

    Ensure valve strokes properly and all positions indicators function correctly when injecting propane to burner

    • Pass
    • Flag
    • Fail

    SURE 100 Valve

    Ensure valve strokes properly and all positions indicators function correctly when unit is above 400 deg F

    • Pass
    • Flag
    • Fail

    SURE 150 Valve

    Ensure valve strokes properly and all positions indicators function correctly when unit is above 400 deg F

    • Pass
    • Flag
    • Fail

    Fuel Train (Enrichment Line)

    Leak test all fuel train connections and address problem at the moment.

    • Pass
    • Flag
    • Fail

    Rotary Gas Meter

    Drain oil on three chambers and refill (Left, Center and Right). Check and replace inlet screened gasket if necessary.

    • Pass
    • Flag
    • Fail

    Interlock Testing

    Check all Interlocks on unit

    Inlet DA, High Temp Switch

    Remove Temperature Switch, heat probe with heat gun and with ohms meter check continuity on common and Normally Close stops when switch reaches 200 degF.

    • Pass
    • Flag
    • Fail

    Outlet DA, High Temp Switch

    Remove Temperature Switch, heat probe with heat gun and with ohms meter check continuity on common and Normally Close stops when switch reaches 200 degF.

    • Pass
    • Flag
    • Fail

    Inlet FA, High Temperature Switch

    Remove Temperature Switch, heat probe with heat gun and with ohms meter check continuity on common and Normally Close stops when switch reaches 200 degF.

    • Pass
    • Flag
    • Fail

    Outlet FA, High Temperature Switch

    Remove Temperature Switch, heat probe with heat gun and with ohms meter check continuity on common and Normally Close stops when switch reaches 200 degF.

    • Pass
    • Flag
    • Fail

    Vapor Blower Failure

    With the unit running and the process inlet closed, turn the vapor blower Hand/Off/Auto switch to the "Off" position on the back panel. Ensure unit shuts down.

    • Pass
    • Flag
    • Fail

    Combustion/Quench Air Blower Failure

    With the unit running and the process inlet closed, turn the Combustion/Quench blower Hand/Off/Auto switch to the "Off" position on the back panel. Ensure unit shuts down.

    • Pass
    • Flag
    • Fail

    Low Supply Gas Pressure

    Close the main valve to the vaporizer and burn out line. If equipped with hand pump testing port, isolate the switch from the fuel train and release pressure from line or use a hand vacuum pump to ensure switch turn the unit down.

    • Pass
    • Flag
    • Fail

    High Supply Gas Pressure

    With unit running, increase the regulator upstream above the set point of the high gas pressure sensor and ensure unit shuts down. If equipped, with hand pump testing port, isolate the switch from the fuel train and use the hand pump port to test the switch to ensure it shuts the unit down.

    • Pass
    • Flag
    • Fail

    Low Pilot Gas Pressure

    With unit running and process inlet closed, shut pilot line fuel valve. Ensure unit shuts down.

    • Pass
    • Flag
    • Fail

    Pilot #1, Pilot #2 Failure. (UV Scanner Shutdown)

    With the unit running and the process inlet valve closed, unscrew and remove UV Scanner from pilot flame sight line, do not expose to direct sunlight. Ensure unit Shuts down.

    • Pass
    • Flag
    • Fail

    Low Combustion/Quench Air pressure Shutdown

    With the unit running and process inlet valve closed, disconnect the tubing connected to the pressure switch. Ensure unit shuts down.

    • Pass
    • Flag
    • Fail

    Process High Pressure Shutdown

    Isolate pressure switch by shutting valve connected to process line, use a hand pump to pressurize the switch to 10 psig. Ensure unit shuts down.

    • Pass
    • Flag
    • Fail

    Combustor High Temperature

    With the unit running and the process inlet closed reset the High temperature reset the high temperature alarm set point to 300 degF. Ensure unit shuts down.

    • Pass
    • Flag
    • Fail

    Combustor Low Temperature

    With the unit running and process inlet closed, set the low setpoint above the test fire temperature. Ensure process valve closes.

    • Pass
    • Flag
    • Fail

    Low Differential Pressure, FA Shutdown.

    With the unit running and the process inlet open, disconnect the tubing on the inlet side of the FA. Ensure the unit shuts down.

    • Pass
    • Flag
    • Fail

    Flame Arrestor

    Check the Flame Arrestor for clogging, remove and clean it if differential across inlet and outlet gauges is greater than 5 wc.

    • Pass
    • Flag
    • Fail

    Detonation Arrestor

    While the unit is at temperature (both manual and actuated valves are open) check the differential pressure across the DA, remove and clean it if differential is greater than 15 wc. Test drains for plugging (open valve and verify suction while the blower is on)

    • Pass
    • Flag
    • Fail

    Flow Gauges

    Test all flow sensors and verify proper readings based on increasing and decreasing process and total flows. Replace if needed.

    • Pass
    • Flag
    • Fail

    Firebox

    Analyze entire exterior firebox wall with temperature gun and notate any part of the wall that exceeds 200°F

    • Pass
    • Flag
    • Fail

    Spare Parts

    Verify Spare Parts are in Job Box

    if the answer is "empty "

    If spare is not stocked due to inventory, let a Maintenance Tech at the Yard know what needs to be ordered and then list below what this unit does not have.

    End Hours

    Unit End Hours

    Meter name
    Unit

    Air Compressor End hours

    Gas Meter End

    Technician Closure Signature

    Technician Sign Off

    Supervisor Closure Approval Signature

    Supervisor Sign Off

    Click here to sign
Source: Envent Corporation (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.