Daikin Magnitude Magnetic Bearing Centrifugal Chillers(Magnitude WME-C): Maintenance

Planned maintenance is the best way to avoid unnecessary expense and inconvenience. This procedure will help you check your system, have it inspected at regular intervals by a qualified service technician. The required frequency of inspections depends upon the total operating time and the indoor and outdoor environmental conditions.
MaintainX
10/24/2021

Daikin Magnitude Magnetic Bearing Centrifugal Chillers(Magnitude WME-C): Maintenance

Planned maintenance is the best way to avoid unnecessary expense and inconvenience. This procedure will help you check your system, have it inspected at regular intervals by a qualified service technician. The required frequency of inspections depends upon the total operating time and the indoor and outdoor environmental conditions.

    The following Maintenance Procedures should only be maintained by qualified service personnel.

    Chiller Maintenance

    DANGER!

    Use approved Lock Out/Tag Out procedures to disconnect power from the unit. Wait 20 minutes after disconnecting power from the unit before opening any compressor access covers. The DC link capacitors store enough energy to cause electrocution.

    Electrical System

    Maintenance of the electrical system involves the general requirement of keeping connections clean and tight. Pump interlocks and flow switches should be checked to be sure they interrupt the control circuit when tripped.

    Cleaning and Preserving

    A common cause of service calls and equipment malfunction is dirt. This can be prevented with normal maintenance.

    The system components most subject to dirt are:

    Water Treatment

    Special care must be taken when utilizing open system water that is usually not treated (such as lakes, rivers, and ponds). The use of untreated water will result in corrosion, erosion, slime buildup, scaling, or algae formation. Water treatment service must be used. Special tube and water head material may be required to reduce damage from corrosion. Daikin Applied is not responsible for damage or faulty operation from untreated or improperly treated water. See “Water Piping” on page 17 for caution stateme

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.