Weekly Diesel Fire Pump Report

MaintainX
10/24/2021

Weekly Diesel Fire Pump Report

    Pump Location:

    Pump Rating:

    GPM @

    PSI @

    RPM

    Completed By:

    Date:

    1. Is fire pump controller on “automatic”?

    • Yes
    • No
    • N / A

    2. Is jockey pump controller on “automatic”?

    • Yes
    • No
    • N / A

    3. Are all jockey pump and fire pump control valves open?

    • Yes
    • No
    • N / A

    4. Is diesel fuel line locked open?

    • Yes
    • No
    • N / A

    5. Is jockey pump running frequency normal?

    • Yes
    • No
    • N / A

    6. Is pump room adequately heated?

    • Yes
    • No
    • N / A

    7. Is adequate combustion air provided?

    • Yes
    • No
    • N / A

    8. Is engine oil at the correct level?

    • Yes
    • No
    • N / A

    9. Is engine coolant at the correct level?

    • Yes
    • No
    • N / A

    10. Is water level and specific gravity correct for both batteries?

    • Yes
    • No
    • N / A

    11. Does battery charger appear to be functioning properly?

    • Yes
    • No
    • N / A

    12. Did fire pump start automatically by a drop in water pressure?

    • Yes
    • No
    • N / A

    Record the following:

    Pump start pressure: psi

    Pump discharge pressure: psi

    Pump suction pressure: psi

    13. Did fire pump start manually on each set of batteries?

    • Yes
    • No
    • N / A

    14. Are pump bearings operating at normal temperature?

    • Yes
    • No
    • N / A

    15. Are pump packing glands leaking sufficient water?

    • Yes
    • No
    • N / A

    16. Is pump free of unusual noises and vibrations?

    • Yes
    • No
    • N / A

    17. Is engine cooling water discharging effectively?

    • Yes
    • No
    • N / A

    18. Is the pump test header drained to prevent freezing?

    • Yes
    • No
    • N / A

    19. Is a charged fire extinguisher in the pump room?

    • Yes
    • No
    • N / A

    20. Is pump room clean and free of combustible materials?

    • Yes
    • No
    • N / A

    21. Did all remote pump signals function properly? (i.e., running, controller not on “automatic”, etc.)

    • Yes
    • No
    • N / A

    22. Was water tank overfilled to verify it’s full, or is reservoir at normal level?

    • Yes
    • No
    • N / A

    23. Was pump run for at least 30 minutes?

    • Yes
    • No
    • N / A

    24. Did engine achieve proper operating temperature, speed & oil pressure?

    • Yes
    • No
    • N / A

    Record the following:

    Water temperature: °F

    Engine speed: rpm

    Oil pressure: psi

    Engine hours: hrs

    25. Is diesel fuel tank at least ¾ full?

    • Yes
    • No
    • N / A

    Record fuel tank level:

    26. Were both the jockey pump and fire pump controllers left on “automatic”?

    • Yes
    • No
    • N / A

    Explain all “No” responses and corrective actions taken: (Ex: 10. Battery A water level low – filled 5/1)

    Reviewed By:

    Date:

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.