Back

Daily Critical Reliability Inspection

The daily inspection ensures the reliability and safety of critical systems within the facility.
312 Lexington KY - Cintas
03/05/2024

Daily Critical Reliability Inspection

The daily inspection ensures the reliability and safety of critical systems within the facility.

    *** LOTO Confirmation Statement - DO NOT EDIT/REMOVE ***

    All hazardous energy has been isolated using LOTO procedures?

    All potential stored or residual energy has been relieved, disconnected, restrained, lowered, and/or otherwise rendered safe?

    Boilers

    Boiler #1 Pressure gauge reading (PSI)

    Boiler #2 Pressure gauge reading (PSI)

    Boiler #1 Exhaust stack temperature (Must not exceed 475F)

    Boiler #2 Exhaust stack temperature (Must not exceed 475F)

    Verify the bottom blowdowns are being completed daily on both boilers.

    ATTACH PICTURE OF LOGSHEET

    • Pass
    • Flag
    • Fail

    Verify the surface blowdown controller is properly maintaining conductivity. Control range is between 3,000 and 3,500 microsiemens per centimeter (µS/cm)

    ATTACH PICTURE OF CONTROLLER DISPLAY

    • Pass
    • Flag
    • Fail

    Verify that daily boiler chemistry tests are being performed

    ATTACH PICTURE OF DAILY LOG

    • Pass
    • Flag
    • Fail

    Inspect boiler feedwater pumps for leaks and proper operation

    • Pass
    • Flag
    • Fail

    Record boiler feedwater tank temperature. Must be between 180-200F.

    Test low water cutoff alarms on both boilers. Both boilers must alarm properly to pass this section.

    ATTACH PICTURE OF BOTH HARTFORD BOILER DAILY TAGS

    • Pass
    • Flag
    • Fail

    Check the levels in boiler feedwater chemical drums. 3/4 empty or below is a flag condition.

    • Pass
    • Flag
    • Fail

    Check condition of flame on boiler #1 during high fire. Must be mostly blue with yellow tips on the flame.

    • Pass
    • Flag
    • Fail

    Check condition of flame on boiler #2 during high fire. Must be mostly blue with yellow tips on the flame.

    • Pass
    • Flag
    • Fail

    Compressed Air System

    Air compressor #1 pressure reading (100-115 psi)

    Air compressor #1 Air-end temperature reading. Must be below 195F.

    Air compressor #2 pressure reading (100-115 psi)

    Air compressor #2 air-end temperature reading.

    Verify the compressed air dryer is working properly. Test the blowdown valve.

    • Pass
    • Flag
    • Fail

    Inspect air receiver tanks for water leaks, air leaks and corrosion. Test the automatic drain valve.

    • Pass
    • Flag
    • Fail

    Wash Alley Chemical System

    Check the level of each chemical barrel in the wash alley. 3/4 empty and below must be flagged.

    • Pass
    • Flag
    • Fail

    Inspect the chemical injection system for air leaks, water leaks and chemical leaks.

    • Pass
    • Flag
    • Fail

    Water Supply

    Inspect wash alley transfer pumps for water leaks.

    • Pass
    • Flag
    • Fail

    Inspect heat reclaimer pumps for water/oil leaks.

    • Pass
    • Flag
    • Fail

    Inspect DAF recirculation pump for water leaks.

    • Pass
    • Flag
    • Fail

    Inspect EQ system transfer pumps for water leaks.

    • Pass
    • Flag
    • Fail

    Inspect heat reclaimer system for water/air leaks.

    • Pass
    • Flag
    • Fail

    Inspect the KEMCO water control system integrity.

    • Pass
    • Flag
    • Fail

    Record the temperature of tempered water shown on the KEMCO control panel. (70-110F)

    Record CITY IN and CITY OUT temperature readings on the KEMCO control panel.

    Record WW IN and WW OUT temperature readings on the KEMCO control panel.

    Record the temperature of HOT WATER shown on the Ludell control panel located on the hot water heater. (140-160F)

    Record the RECLAIMER APPROACH temperature differential shown on the KEMCO control panel.

    Verify water levels on the KEMCO control panel match actual levels in our water storage tanks. With a tape measure, check the top of the tank transducer to the sight glass level. It must read within 2 inches.

    • Pass
    • Flag
    • Fail

    Verify the EQ system is running, and tank blower is constantly running.

    • Pass
    • Flag
    • Fail

    Verify the wastewater pit blowers are running correctly, and air filters are not clogged.

    • Pass
    • Flag
    • Fail

    Verify the DAF mixers are running properly

    • Pass
    • Flag
    • Fail

    Verify the wash alley trench is being cleaned regularly. Report any messes or pit doors being left open.

    • Pass
    • Flag
    • Fail

    Water Softeners

    Main softeners both have salt in the brine tank

    • Pass
    • Flag
    • Fail

    Inspect both softeners for water leaks

    • Pass
    • Flag
    • Fail

    Verify both brine tank fill valves are working correctly. Water should not be above float valve.

    • Pass
    • Flag
    • Fail

    Meter Readings

    Natural gas meter reading

    Electric meter reading

    EQ to DAF flow meter reading

    City water #1 reading

    City water #2 reading

Source: 312 Lexington KY - Cintas (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.