Back

Carrier® Dedicated Outdoor Air Unit 62X: Quarterly Maintenance

This quarterly maintenance helps you check the settings (controls, operating temperatures, operating pressures, power and control voltages) and operation.
MaintainX
09/15/2022

Carrier® Dedicated Outdoor Air Unit 62X: Quarterly Maintenance

This quarterly maintenance helps you check the settings (controls, operating temperatures, operating pressures, power and control voltages) and operation.

    MAINTENANCE

    Prior to any maintenance or service to the unit, shut off, lockout, and tagout the electrical disconnect and fuel valve (if applicable) that supplies the unit in accordance with OSHA regulations and, if the unit includes electric or gas heat, allow ample time for the unit to cool. After maintenance is performed or the unit is serviced, the unit shall be re-commissioned per the start-up procedure.

    Installation Code and Quarterly Inspections

    All installation and service of Carrier’s 62X equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Carrier, as well as conform to all requirements set forth in the manuals and all applicable governmental authorities pertaining to the installation, service, operation, and labeling of the equipment.

    To help facilitate optimum performance and safety, Carrier recommends that a qualified contractor conducts, at a minimum, quarterly inspections of your 62X Series equipment and perform service where necessary, using only replacements parts sold and supplied by Carrier.

    QUARTERLY

    Follow the entire start-up procedure at this time and check settings (controls, operating temperatures, operating pressures, power, and control voltages) and operation.

    Unit Exterior

    CABINET EXTERIOR

    UNIT LOCATION

    Direct Drive Supply and Exhaust Fans

    BLOWER WHEEL

    MOTORS

    Inspection

    Lubrication

    • Screenshot2021-01-15at7.04.19AM.png

    Lubricating Instructions

    Before greasing, be sure fittings are clean and free from dirt. Remove grease relief plug or plate and, using a low-pressure grease gun, pump in the required grease. Do not over-grease. Re-lubrication intervals are specified in Table 12. After re-lubricating, allow motor to run for 10 minutes before replacing relief hardware.

    IMPORTANT: In general, it is not recommended to mix greases of different brands. The mixing of different types of thickeners may destroy the composition and physical properties of the grease. In the event that a different grease is required by the end user, the following steps can be taken. Using the Lubricating Instructions, open grease outlet and purge the system as much as possible of the old or unwanted grease. Repeat this same operation after one week of service.

    Condensing Fans

    Refrigeration Circuit Components

    EVAPORATOR COIL

    CONDENSER COIL

    COMPRESSORS

    Condensate Drain Pan and Drain

    Dampers

    DAMPER MOTOR/LINKAGES

    Energy Conservation Wheel

    BEARINGS

    DRIVE MOTOR

    DRIVE BELTS

    SEALS

    WHEEL

    The wheel is somewhat self-cleaning through its normal action of rotating in and out of counter current airflow streams.

    In the event that routine quarterly inspection indicates that there is dirt or dust buildup within the wheel causing an excessive pressure drop, then wheel cleaning should be performed as follows:

    Gas Heater

    GAS LINE

    Check for gas leaks

      MANUAL SAFETY SHUT OFF VALVE

      Check for gas leaks.

        DIRECT SPARK IGNITER

        Check for cracked ceramics, excessive carbon residue, or erosion of the electrode. Replace as required.

          GAS VALVE

          Check that gas valve seat is not leaking.

            BURNERS

            Soft brush or vacuum inside burner, at burner ports, and at air inlet between burner and manifold pipe to eliminate accumulation of lint and/or dirt.

              HEAT EXCHANGER

              Inspect for cracks, sagging, bending, or distortion. Clean with vacuum and/or stiff brush.

                DRAFT INDUCER

                Clean with compressed air or vacuum.

                  VENT PIPE/TERMINAL

                  Venting must be intact. Using a flashlight, look for obstructions, cracks on the pipe, gaps in the sealed areas, or corrosion. Clean vent terminal.

                    CONDENSATION DRAIN

                    Check for blockages.

                      Electric Heater Wiring and Wiring Connections

                      Check all wiring connections. Tighten as necessary. Check internal wiring. Replace as necessary with type THHN 221°F (105°C), 600V, 16-gauge wire or equivalent.

                        CONTROL PANEL

                        Check heater control panel for dust/dirt and moisture. Clean as necessary.

                          HEATING ELEMENTS

                          Check heating elements for dust/dirt buildup and/or broken elements. Replace elements and/or clean elements with low pressure air as necessary. Check element male/female chassis insulators for breaks and/or cracks. Replace as necessary. Check element support frame insulators. Replace missing or broken insulators as necessary

                            Filters

                            Filters should be checked for dirt restriction on a monthly basis (or as required). Replace filters with filters of equal specification when they appear dirty.

                            Source: MaintainX (Community Member)

                            Please note that any procedure, checklist, or other document available in the MaintainX Global Procedure Library is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.